FXOQ-M 30
Installation
How to Connect Wiring
• Connect the wiring only after finishing
the refrigerant piping work.
• First make sure all power supply is iso-
lated.
• As shown in Figure 17, loosen the 4
screws on the control box lid, remove
it, and conduct wiring work.
• Once all wiring is completed, attach the
control box lid and secure it with
screws.
• Remote sensor lead wire:
1. Connect to (X13A) on AIP. Connec-
tor Color: White, Size: Large.
2. Bundle the remote sensor lead wire
using the included clamp (1).
3. Make sure no tension is present on
the remote sensor lead wire coming
out of the unit.
• Thermistor Lead Wire (8):
1. Connect to (X21A) on AIP (Connec-
tor Color: White, Size: Small).
2. Bundle the thermistor lead wire
using the included clamp (1).
3. Make sure no tension is present on
the thermistor lead wire coming out
of the unit.
4. For fixing the Liquid Line Ther-
mistor, refer to Step 7.
• Power supply wiring and ground wire:
1. Connect the wiring between the
Electronic Expansion Valve unit and
the Vertical Air Handling unit. The
power source is supplied from the
Vertical Air Handling unit.
2. Connect the wiring to L1 and L2 on
the power supply terminal block
(X11M). Also connect the ground
wire to the ground terminal. Take the
wiring and the ground wire into the
unit through the provided cabling
hole and firmly secure them using
the included clamp (1).
• Transmission wiring for Vertical Air
Handling Unit:
1.Connect the wiring between the Elec-
tronic Expansion Valve unit and the
Vertical Air Handling unit
2. Connect the wires to 1, 2, 3, and 4
on the operation terminal (X13M).
Take the wires into the unit through
the provided cabling hole and firmly
secure them using the included
clamp (1).
• Transmission wiring for remote control
and outdoor unit:
1. Connect the remote control wiring to
P1 and P2 on the transmission ter-
minal block (X12M)
2. Connect the outdoor unit wiring to
F1 and F2 on the transmission termi-
nal block(X12M)
3. Take the wiring through the provided cabling hole and secure the remote
control wiring and outdoor unit wiring using the included clamp (1).
CAUTION
Do not, under any circumstances, connect the power supply wiring to the trans-
mission block (F1, F2) as this may cause damage to the entire system.