Specifications

Electric Characteristics EDUS39-600-F20_b
15 FXOQ-M
7. Electric Characteristics
UNITS POWER SUPPLY
FAN
MOTOR
MODEL Hz VOLTS
VOLTAGE
RANGE
MCA MFA FLA
12Type+BEQ12MVJLR1
60 208
Max. 229
Min. 187
1.5
15
1.1
18Type+BEQ18MVJLR1
24Type+BEQ24MVJLR1 2.8 2.1
30Type+BEQ30MVJLR1 3.4 2.6
36Type+BEQ36MVJLR1 3.9 3.0
42Type+BEQ48MVJLR1
5.2 4.0
48Type+BEQ48MVJLR1
NOTE:
1. The above Table of Electrical Characteristics refers to the Electronics Expansion Valve unit and the Vertical Air
Handling unit.
2. See the technical documents for other details.
3. See the Electrical Characteristics of the Vertical Air Handling Unit Installation Manual.
4. Use special caution with models with electric heaters, both MCA and MFA.
SPECIFIATIONS FOR FIELD SUPPLIED FUSE AND WIRE:
MODEL POWER SUPPLY WIRING TRANSMISSION WIRING
Electronic Expansion Valve unit + Vertical Air
Handling Unit
Field Fuse Wire Size Wire Size
15A UL1015
Size must
comply with
local codes.
2-Conductor,
stranded non-
shielded copper
cable/ PVC or vinyl
jacket
AWG 18
1. Select the particular size of eletcial wire for proper line in accordance with the standards of the given nation and
region.
2. Allowable length of the transmission wire should be as follows:
Between Electronic Expansion Valve unit and Vertical Handling Unit:
Maximum 10 feet (total wiring length 6562 ft.)
3. Insulated thickness: 1/16” or more
4. Up to 16 branches are possible for unit-to cabling. No branch is allowed after first branch. See Figure 16.