Specifications

Actassi Enclosures
VDS
19" server
Robust and ventilated
Technical characteristics
Folded and welded sheet-steel enclosure, textured, RAL 9011 black
epoxy-polyester powder paint.
Earth continuity guaranteed, according to the standard.
Allowed air ow above 80%
Acceptable static load: 750 kg.
Color:
Black (RAL9011)
Ingress Protection : IP20
Object size protected against > 12,5mm
No liquid protected
Impact Potection : IK10
Impact energy = 20 joules
Certications: In compliance with the directive RoHs, with the 19" standard
IEC60297-3-100 and EIA-310D
Rack composition
Top and bottom frames, mechanically assembled by Torx screws to the vertical
structure uprights, thus forming a rigid framework.
Base without blanking plate (page XX).
Cut-out roof, closed with a blanking plate with dismountable brush gasket.
Reversible microperforated front and rear door, opening to 180°, closure at 2 points
with a handle and a key 333. Hinges on the right as standard.
Side panels with no louvres, with quick installation and removal, closing by latches.
Top and bottom side cable entries ush with the structure.
Top and bottom side knock-out areas for cable entry, with a width of 800 mm.
Large opening on the bottom and large knock-out area on the rear for cable entry.
Levelling feet installed.
Four 19" uprights made from treated steel, installed 100 mm back from the front
plate and depth-adjustable in steps of 25 mm.
Earthing kit installed.
Delivered on a pallet covered with lm.
Composition of the rack without side panels
Exactly the same composition as the above rack, but without the side panels.
Coupling kit not supplied.
In the event of coupling, use coupling kit ref. NSYCUNVDA and brush gasket (ref.
NSYCUNPL600, NSYCUNPL800 or NSYCUNPL1000) to close the cable entry left
by the 2 side panels.
Introduction
Number of U
Ext. dimensions (mm)
Rack
Height Width Depth
42U 2000 600 1000 NSYVDS42U610N
42U 2000 800 800 NSYVDS42U88N
42U 2000 800 1000 NSYVDS42U810N
Selection guide
Network Connectivity | 04.2012 Actassi | 113