Fault Possible causes Measures
Drive runs
roughly
Kp (speed controller) too high
Tn (speed controller) too low
ARLPF / ARHPF too low
ARLP2 too low
reduce Kp (speed controller)
use motor default value for
Tn (speed controller)
increase ARLPF / ARHPF
increase ARLP2
Axis drifts at
setpoint = 0V
offset not correctly adjusted for
analog setpoint provision
AGND not joined to the
controller-GND of the controls
adjust offset (analog I/O)
join AGND and controller-GND
n12 message:
Motor default
values loaded
Motor numbers stored in the
encoder and amplifier do not
match the parameters that have
been set
default values for the motor
have been loaded, SAVE
automatically stores the
motor number in the EEPROM
n14 message:
SinCos feed
-
back
SinCos commutation
(wake&shake) not completed
ENABLE the amplifier