Note: Do not draw more than 15,000 watts from the receptacles with all of the
lights on or the lights will turn off. Load to at least 50% of the rated load to prevent
wet stacking.
Circuit
breakers
Circuit breakers (e) on the back of the receptacle panel protect the GFI
receptacles. The GFI receptacles should be tested for proper operation each time
they are used.
Testing a GFI
To test a GFI:
1. Push the test button in. The reset button should pop out. Power to the
receptacle is now off.
2. To restore power to the receptacle, push the reset button.
NOTICE: If the reset button does not pop out, the GFI is defective. Do not use the
receptacle until the problem can be corrected.
If the reset button pops out during use, check the generator and attachments for
defects.
Model
Callout Quantity
Description
LTW20Z-1
a 4 120V Ground Fault Interrupt (GFI) convenience
receptacle
b 2 120/240V single phase receptacle
c 1 120/240V single phase receptacle
d 3 Circuit breaker for 120/240V and 240V single phase
receptacle
e 4 Circuit breaker for 120V GFI receptacle
LTW20Z-3
a 4 120V Ground Fault Interrupt (GFI) convenience
receptacle
b 2 120/208V single phase receptacle
c 1 120/208V three phase 4-pole receptacle
d 3 Circuit breaker for 120/208V single phase recepta-
cle and 120/208V three phase receptacle
e 4 Circuit breaker for 120V GFI receptacle