4. To configure data buffer storage on a syslog server in the Syslog Data Buffering Settings
section; select a facility number from the drop-down menu: Log Local 0, Log Local 1, Log
Local 2, Log Local 3, Log Local 4 or Log Local 5.
5. Click Save.
Appliance logging
To configure appliance logging:
1. Click Enable appliance session data logging.
a. Select the destination for appliance session data logs from the pull-down menu.
Choices are Local, NFS, Syslog and DSView.
b. Enable or disable timestamping the appliance session data logs.
2. Click Enable appliance session data logging alerts.
3. Enter the desired alert strings (up to ten) in the fields provided.
4. Click Save.
Sensors
The console server has sensors that monitor the internal temperature. You can specify an
operating range for the console server that fits its environment.
CAUTION: Do not use values that exceed the maximum and minimum temperatures. See "Technical
Specifications " on page 73.
To configure the temperature sensors:
1. Click Events and Logs - Sensors.
2. In the Maximum Temperature field, enter the temperature in degrees Celsius that, if
exceeded, will generate an event notification.
3. In the Maximum Temperature Threshold field, enter the temperature threshold in degrees
Celsius below the maximum temperature.
NOTE: The Maximum Temperature Threshold field will define a region around the maximum temperature. When
the temperature exceeds the Maximum Temperature plus Threshold, an event notification will be generated. When
the temperature falls below the Maximum Temperature minus Threshold, an even notification that the console
server has returned to normal operating temperature will be generated. This is also true for setting the minimum
temperature threshold.
4. In the Minimum Temperature field, enter the temperature in degrees Celsius that, if the
console server’s temperature falls below, will generate an event notification.
64 Cyclades™ ACS 6000 Advanced Console Server Installation/Administration/User Guide