User guide

Chapter 3: Accessing the ACS 6000 Console Server via the Web Manager 55
5. Click Save.
To view a PDU’s information:
1. Select Power Management - PDUs.
2. Click the name of the PDU you want to view or manage.
3. The Outlet Table with power controls window appears and the Side Navigation Bar displays a
list of options.
4. To manage outlets of PDU:
a. Check the box(es) of the outlet number(s) you want to manage.
b. Click On, Off, Cycle, Lock or Unlock to perform that function for the selected outlet(s).
5. Click Information in the Side Navigation Bar to view a PDU’s information.
6. Click Current, Voltage, Power Consumption, Cumulative Power or Environment in the Side
Navigation Bar to view a table with appropriate information. Click Reset Values to clear Max,
Min and Average values.
To upgrade firmware (Cyclades PM PDU only):
1. Click Overview in the Side Navigation Bar and click on Upgrade Firmware.
2. Fill all fields with correct information and click Download to download the firmware to the
ACS 6000 console server.
3. When the download finishes, the Install PM Firmware screen appears. If the version
information is correct, click Upgrade Now to start the upgrade of the firmware in the PDU.
4. When the upgrade finishes, the Finish Upgrade screen appears with the result of the upgrade
action. Click Finish.
To manage outlets on a PDU:
1. Click Settings to expand the Side Navigation Bar.
2. Click Outlets.
3. Click on an outlet number to change its settings. You can change the Name, Post On Delay,
Post Off Delay, Current Critical Threshold, Current Warning Threshold and Current Low
Warning Threshold.Click Save, then click Close.
-or-
Check two or more boxes next to the outlets for which you want to change settings. Click Edit.
You can change the Prefix Name (the outlet name will be Prefix Name and the Suffix), Post
On Delay, Post Off Delay, Current Critical Threshold, Current Warning Threshold and Current
Low Warning Threshold. Click Save.
4. Click PDU to see PDU settings. You can change the Nominal Voltage, Power Factor and
Current Threshold(s). Click Save when finished.
5. Click Phases or Banks.