Product specifications
Environmental Requirements
106
Environmental Requirements
The Avid ISIS and Interplay hardware and switches are intended for use computer-room environments. They are
not intended for use on top of desks or in open office environments. When you select a location, make sure that the
location meets the following requirements:
• A sturdy, level floor, not subject to vibration.
• Away from high-traffic areas.
• Clean and free from dust, smoke, or other airborne contaminants.
• No significant temperature changes. Choose a location where the temperature does not vary more than 18°F
(7.78°C) per hour.
• No significant humidity changes. A location with approximately 40 percent humidity can prevent problems
stemming from electrostatic discharge.
• Adequate space in front of and behind the rack. You must be able to connect cables and service parts of your
hardware. It also needs adequate airflow for cooling.
Cisco Catalyst 6500-E series 100 to 240 V ac 50 to 60 Hz 6503
1400 W
6504
2700 W
6506 to 6513
1 to 5 power supplies
2500 W to 8700 W
6503
4777 BTU/hr
6504
9213 BTU/hr
5 power supplies
29,686 BTU/hr
Cisco Nexus 7000 series 110 to 240 V ac 50 to 60 Hz Depending on the number
of power supplies (1-4)
and mode
110v —
1450 to 2900 W
220v —
3000 to 6000 W
7004
9737 BTU/hr
7009
28,101 BTU/hr
7010
35,162 BTU/hr
7018
51,195 BTU/hr
Dell Networking
N3048
N3024
S25N
S25P
S60
S4810
100 to 240 V ac
100 to 240 V ac
110 to 240 V ac
110 to 240 V ac
110 to 240 V ac
110 to 240 V ac
50 to 60 Hz
50 to 60 Hz
50 to 60 Hz
50 to 60 Hz
50 to 60 Hz
47 to 63 Hz
200 W (maximum)
200 W (maximum)
102 W (maximum)
90 W (maximum)
225 W (maximum)
270 W (maximum)
221 BTU/hr
151 BTU/hr
349 BTU/hr
305 BTU/hr
531 BTU/hr
921 BTU/hr
Foundry
FESX424 and FESX624
100 V ac, 3.5A
240 V ac, 1.5A
50 to 60 Hz 220 W (per supply) 750 BTU/hr
(per supply)
Switch Electrical Specifications (Continued)
Switch Voltage Frequency Watts (Maximum) BTUs