0040-17001-01 (Revision W) Installation Checkout Page 3-26
e. Resolution (ft): Select > 25 or <=25 based on the encoder increment rate.
The resolution is automatically changed to > 25 ft. when Gillham Interface source is
selected.
Selecting > 25 sets the Altitude Thresholds for GPS altitude and Pressure Altitude to 150ft.
Selecting <=25 sets the Altitude Thresholds for GPS altitude and Pressure Altitude to 50ft.
3. Click on the Apply button after all information is entered. This information is saved to the
configuration module.
4. Ensure the "Write to DCM succeeded. Write to NVM backup succeeded" message is displayed in the
lower communications bar.
3.7.3 I/O Options Misc
From the MPC (MAT) select Setup…ConfigurationModifyI/O OptionsMisc. See Figure 3-12.
Enter the information specific to the installation for the intended certification.
NGT-9000 NGT-9000R
Figure 3-12: MPC (MAT)I/O Options Misc
1. Control Panel: This option is shown as Touch Screen for NGT-9000 or CP-2500 and ARINC 429
(Release 3.2 and later) for NGT-9000R.
Touch Screen: This is set for Touchscreen for panel mount NGT-9000.
CP-2500: This option must be selected for the remote mount NGT-9000R installed with a CP-
2500.
ARINC 429: Only applicable to a remote mount NGT-9000R, this option is selected for
ARINC 429 Control Panels. Note: this option includes Transponder control only.
RS-232 Baud Rate: 9600 baud rate must be selected for the CP-2500 and is normally selected to
9600 for other controllers.