User's Manual

Table 2: Control modules overview
Module
type
Description Additional Info
FP-1601 Control module with IP
interface
Interface module between the I/O modules and
DECT Messenger. Controls up to 9 I/O modules
directly.
FP-1000 Control module with
V.24 interface
Interface module between the I/O modules and
DECT Messenger. Controls up to 9 I/O modules
directly.
Up to 24 FP-1001 modules can be connected
using RS485 bus to expand the system with extra
I/O modules.
FP-1001 Expansion control
module
Must be connected to the RS485 interface on the
FP-1000. One FP-1001 can control up to 9 I/O
modules. The maximum number of FP-1001
modules one RS485 bus is 24
PS-2 Power Supply 24 Volts DC
Table 3: I/O modules overview
Module
type
Description Additional Info
FP-AI-100 Analogue input 8 Analogue inputs each can be set to one of the
following ranges: 30V, 15V, 5V, 1V, 0-30V, 0-15V,
0-5V, 0-1V, 20mA, 0- 20mA, 4-20mA.
FP-DI-300 Digital input 8 discrete input channels. These inputs are sinking
inputs for 24VDC
FP-DI-301 Digital input 16 discrete input channels. These inputs are
sinking inputs for 24VDC
FP-DI-330 Digital input 8 discrete input channels. Universal inputs work
with any voltage from 5V TTL up to 250VDC/VAC.
Compatible with sourcing, sinking, or power
sensing applications.
FP-DO-400 Digital output 8 discrete output channels. Max. 2A per output,
max 8A per module. Maximum voltage 30VDC
FP-DO-401 Digital output 16 discrete output channels. Max. 2A per output,
max 8A per module. Maximum voltage 30VDC
Note:
For each I/O module, one Terminal Base (TB-1) is required.
Preparing external devices
20 DECT Messenger Installation and Commissioning — Book 1 March 2012