User's Manual
316 Module - eCAP
When HERSTEL occurs a general reset of all ARITECH alarms is issued
for *ALL groups and *ALL alarm descriptions.
Note: This protocol usually requires project-based consulting services
and customizing.
BEMAC
Valid manufacturer is BEMAC, valid model is DIANA 1 and DIANA 2.
Bemac is based upon installation Clinique St-Vincent Rocourt.
Figure 68
Sample Bemac protocol data
Bemac alarms contain three fields, a pager number, a message and a tone
code. Alarms are sent with group equal to the first parameter (for example,
866). The message is retrieved from the second parameter (for example,
LOC 101B). When the third parameter is 0 the message is reset. When
the message is RESET all messages for all groups are reset; in other
cases only the specific message for the specified group is reset. When
the third parameter is a value other than 0, the message is set. During set
the alarm description is BEMAC_x, where x is the specified tone code (for
example, tone code 3 sets message with alarm description BEMAC_3.
ELDAD
Valid manufacturer is ELDAD, valid model is specified through a special
syntax, for example, L:48-0:RC-1:SR-2:SS-3:SS-4SR. Note that the model
is built upon components having syntax A:BB and separated with a hyphen
(-).
• L:xx denotes that the length of an alpha-message is xx bytes. For
example, L:48 means that alpha-messages are 48 bytes long, L:24
denotes alpha-messages are 24 bytes long.
• 0:xx specifies behavior of tone code 0, 1:xx specified behavior of tone
code 1, 2:xx specifies behavior of tone code 2, and so on.