User's Manual

Overview 311
Figure 65
eCAP Connection tab
Because the eCAP is designed to handle asynchronous serial
communications with a number of alarm systems, the eCAP requires
configuration settings to start processing. These values are returned
through the <cfgrpy> reply that is sent on return of the <cfgrqs> request.
Some parameters refer to asynchronous communication settings (for
example, port number, baud rate, data bits, parity bits, stop bits, and so
on); others refer to general information settings (for example, logging
parameters); the rest are parameters that actually determine the alarm
system (for example, manufacturer, model, bidirectional, and so on).
Note: The values shown in Figure 65 "eCAP Connection tab" (page
311) are received from the DECT Messenger database: from the
eKERNEL_INPGM table, eCAP_generic table, and the eKERNEL_SITE
table.
At startup, the eCAP.exe appears the specified COM port with the
specified settings. The COM port specified must be available, be set
to use a valid baud rate, and so on. A physical connection must exist
between the specified COM port and the external alarm system through
a properly wired serial cable. In many cases, alarm systems support
a limited number of control signals (for example, ground and send),
so consult the alarm system vendor on cable specifications. In most
cases, you can use a standard null-modem cable. If no more COM ports
are available, extra hardware (such as DigiBoard PC/4e or DigiBoard
PC/8e) is needed to provide extra serial ports. Check compatibility issues
(supported by operating system, driver available, and so on) and hardware
requirements (memory, available slots, IRQ conflicts, and so on) before
ordering or configuring a system.
Nortel Communication Server 1000
DECT Messenger Installation and Commissioning — Book 1
NN43120-301 02.01 4 June 2010
Copyright © 2003-2010 Nortel Networks. All Rights Reserved.
.