Why Does the FP-1600/2000/2010 Have Problems Configuring in
Computers with 2 Ethernet Ports?
Product Group: FieldPoint Hardware
Product Name: FP-1600
Version/Revision: N/A
Problem: In computers that use two ethernet cards, attempts to configure
an FP-1600/2000/2010 sometimes results in the message, no response
from module. I am trying to assign an IP address to my FieldPoint 1600
module. It shows up as Unconfigured, but when I try to assign the IP
address, I see the message Module not responding. What is wrong?
Solution: This can be caused by a variety of factors. First, in a two
ethernet port system, both ports must be configured with mutually
exclusive subnets. There can be no overlap in the subnet addresses of
the two ports; however, even when this is properly configured, there are
frequently problems with configuring the FP-1600/2000/2010.
This is due to a limitation with the Microsoft TCP/IP stack (as tested under
Windows 98 and Windows NT4 SP5). A typical message contains source,
destination, and data information. When sending out broadcast messages,
the Microsoft TCP/IP stack places the same source address in the
messages going out both ports (that is, the address of the first port in the
stack is used), rather than using the appropriate source address for each
port. Thus, an FP-1600/2000/2010 trying to respond to the message is
trying to respond to the wrong port, because that is the address received.
This happens only with broadcast messages. FieldPoint uses broadcast
messages while configuring a module. When the module is configured,
point-to-point messages are used to communicate with the module.
There are several ways to work around the broadcast limitation while
configuring the module.
• Workaround 1: Place the module on the other ethernet card for
configuration.
• Workaround: 2: Use a computer that has only one ethernet card for
configuration.
• Workaround 3: Remove the ethernet drivers for both cards, and then
reinstall the drivers with the board that talks to the FP-1600 being
installed first.
• Workaround 4: If your system uses two plug-in ethernet cards (not
integrated on the computer motherboard), and then swap the positions
of the two cards.