User's Manual

130 DECT Messenger Customer Engineer Manual
8 Configure the Watchdog
Select the time period
Select the COM port
Note 1: If you followed the instructions in Step 1 of this
procedure, you set the Watchdog timer to 30 seconds.
Therefore, you must fill in a time period that is significantly
lower than this value, for example, 8 seconds.
Note 2: After selecting the COM port, keep in mind that other
Modules use COM ports as well, such as eCAP, eESPA, eIO.
9 Verify correct operation.
To test the operation of the Watchdog, set the time in the
eKERNEL_SITE table to a higher value (for example, 40
seconds). As a result, the signal does not arrive within 30
seconds, the Watchdog timer expires, and the alarm relay
contacts are closed. After you finish testing, remember to set the
time value in the eKERNEL_SITE table back to its original value
(for example, 10 seconds).
Nortel Communication Server 1000
DECT Messenger Fundamentals
NN43120-120 02.01
11 May 2009
Copyright © 2003-2009 Nortel Networks
.