Specifications

INSERT INSTALLATION (CONT.) - For qualified installers only! PAGE 15
Insert Placement
The Insert Must be
Placed 11-1/4" into
the Fireplace.
Run the brown and red
wire (for the on/off
switch) to the right side
along the facing.
Run the power cord to
either side of the insert
along the facing.
The insert must be in place with
the gas line and vent attached
prior to installing the panels.
Min. 27-3/4" WIde (includes 6" for gas
line installation)
Min. 21-5/8" Tall
(includes 2" for
vent installation)
The gas line faces to the rear
and its center is 4-1/4" back
from the fireplace opening, 1-
5/8" above the hearth, and 7-
1/2" from the center of the
insert.
NOTE:
When using the 45° vent, an
additional 4" is required
behind the rear edge of the
baseplate for vent hook-up.
Use the leveling bolts for
fireplaces with recessed
floors (included with the
surround panels).
Insert must be placed so no combustibles are within, or can swing within 36" of the front of the
heater (e.g. drapes, doors)
The insert may be placed inside a masonry fireplace or listed zero-clearance (metal) fireplace
The insert must be installed in a level, undamaged fireplace (damage must be repaired prior to
installation). Use the included leveling bolts to level the insert in fireplaces with recessed floors.
The insert must maintain 10" clearance to sidewalls (measure from the upper top)
Non-combustible facing (e.g. brick, tile) must extend 8" minimum from the side and 12" to the top of
the insert (measure from the upper top)
Combustible mantles must be a minimum 17-1/2" above the top of the insert (measure from the
upper top)
+ Clearances may be reduced by methods specified in NFPA 211, listed wall shields or other means
approved by local building or fire officials.
Floor Protection
The heater must be installed on a non-combustible hearth and may not extend over combustible
flooring