STOVE INSTALLATION (CONT.) - For qualified installers only! PAGE 11
Gas Line Install
! The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI Z223.1
and the requirements listed below.
! The heater and gas control valve must be disconnected from the gas supply piping during any
pressure testing of that system at test pressures in excess of 1/2 psig. For pressures under 1/2 psig,
isolate the gas supply piping by closing the manual shutoff valve.
Leak test all gas line joints and the gas control valve prior to and after starting the heater.
F
uel
This heater is designed either for
natural gas or for propane (but not
for both). Check the sticker on the
top of the gas control valve to make
sure the correct fuel is used.
G
as Line Connection
The gas inlet accepts a 3/8" F.P.T.
Fitting
The location of the gas inlet is
shown to the right
A manual shutoff valve is required
for installation (it must be located
within 3' of the heater)
12-3/4"
4-3/4"1-1/2"
Gas Inlet Pressure
With the heater off, the inlet pressure must meet the requirements listed in the table below
? If the pressure is not sufficient, make sure the piping used is large enough and the total gas load for
the residence does not exceed the amount supplied.
? The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank)
should supply gas at the suggested input pressure listed below. Contact the local gas supplier if the
regulator is at an improper pressure.
Minimum Input Pressure
Natural Gas 5.5" W.C.
Propane 11" W.C.