Installation manual
2 Introduction
© Travis Industries 4050714 100-01173_001
Overview
This manual details the installation
requirements for the 864TRV fireplace. For
operating and maintenance instructions, refer to
the 864TRV Owner's Manual (part # 100-01168).
Listing Details
This appliance was listed by OMNI Test Labs to
ANSI Z21.88 - report # 028-F-59-5. The listing
label is attached to the appliance near the gas
control valve. A copy is shown to the right.
ICBO Approval
This appliance was listed by OMNI Test Labs -
ICBO # TL130.
Massachusetts Approval
This manual has been submitted to the
Massachusetts Board of State Examiners of
Plumbers and Gas Fitters
National Fireplace Institute
864TRV
Vented Gas Fireplace Heater
Tested to: ANSI Z21.88b-2003 “Vented Gas Fireplace Heater” and UL307b-1995 “Gas Burning Heating Appliances for Manufactured Homes”.
This appliance must be installed in accordance with local codes, if any; if none, follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54.
Installation in Manufactured or Mobile Homes must conform with Manufactured Home Construction and Safety Standard, Title 24 CFR,
Part 3280.
This vented gas fireplace heater is equipped at the factory for use with natural gas. If conversion to propane (LP) is desired, the optional
factory conversion kit must be used.
This appliance is only for use with the type of gas indicated on the rating plate and may be installed in an aftermarket,
permanently located, manufactured (mobile) home where not prohibited by local codes. See owner’s manual for details. This appliance is
not convertible for use with other gases, unless a certified kit is used.
This vented gas fireplace heater is not for use with air filters.
Keep burner and control compartment clean. See installation and operating instructions accompanying appliance.
This appliance must be properly connected to a venting system in accordance with the manufacturer’s installation instructions. Use only
approved coaxial direct vent system to vent this appliance to the exterior. See owner’s manual for approved brands of venting.
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to the owner’s
information manual provided with this appliance. For assistance or additional information consult a qualified installer, service agency or
the gas supplier.
VENTED GAS FIREPLACE HEATER – NOT FOR USE WITH SOLID FUEL
CAUTION:
Hot while in operation. Do not touch. Severe burns may result.
Keep children, clothing, furniture, gasoline and other liquids having flammable vapors away.
Do not operate this appliance with glass removed, cracked or broken. Replacement of the
panel(s) should be done by a licensed or qualified service person.
Minimum Clearances to Combustibles
Fireplace to Adjacent Wall . . . . . . . 1” Top to enclosure (from stand-offs). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0”
Wood Floor Beneath Fireplace . . . 0” Sides to enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.5”
Back to enclosure . . . . . . . . . . . . . . 0.5” Base of Fireplace to an 8” Mantel (see manual for other mantel depths). . . 44.75”
L.P
.
N.G.
L.P
.
N.G.
Input Rate on “HI” (BTU/Hr)............ 31,000 31,000 Minimum Inlet Pressure (inches W.C.)............... 11” 5.5”
Input Rate on “LO” (BTU/Hr)........... 8,000 10,000 Maximum Inlet Pressure (inches W.C.).............. 13” 7”
Manifold Pressure on “HI” (inches W.C.) .......... 10” 3.5”
For natural gas when equipped with the following drill size orifice: DMS 49 Front - 49 Back
For propane when equipped with the following drill size orifice: DMS 57 Front - 57 Back
This appliance is equipped for use only at altitudes 0-2,000 feet.
For altitudes above 2,000 feet, the vent configuration, orifice, or combination of both may need to be changed.
See the owner’s manual for information on making these changes.
Electrical Rating: 115v, 1.5 Amps, 60 Hz
4800 Harbour Pointe Blvd. SW Mukilteo, WA 98275
Manufacture 2005 Jan. Apr. Jul. Oct.
Date: 2006 Feb. May Aug. Nov.
2007 Mar. Jun. Sep. Dec.
IGN 549
Report No. 028-F-59-5
Certified for USA