Owner`s manual
Stove Installation (for qualified installers only) 11
© Travis Industries 100-01179 4081028
Chimney Requirements
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
UL 103 HT Chimney must be used from the first ceiling or floor penetration to the chimney cap.
Use 6" diameter type UL 103 HT chimney from one manufacturer (do not mix brands) or code
approved masonry chimney with a flue liner.
Chimney must be fastened to each adjoining section.
Follow the chimney manufacturer's clearances and requirements.
Use the chimney manufacturer's fire stops, attic guards, roof supports, and flashings when passing
through a ceiling
No more than 180
o
of elbows (two 90
o
elbows, or two 45
o
& one 90
o
elbow, etc.) may be used for the
entire system (connector and chimney).
NOTE: Additional elbows may be allowed if draft is sufficient. Whenever elbows are used the draft is
adversely affected. Additional chimney height may be required to boost draft.
Chimney Cap
(See the section "Chimney Termination
Requirements" for more details)
Factory Built Chimney Sections
Minimum Air Space to Combustibles
(See Chimney Manufacturer's
Instructions)
Floor Penetration Equipment
(Attic Radiation Shield with Chimney Support)
Reduced Clearance Chimney
Connector Sections
Roof Penetration Equipment (Roof
Radiation Shield, Flashing, Storm Collar)
}
}
Stove Clearance
(as outlined in this manual)
}
Standard residential installations with reduced
clearance connector may use the clearance determined by
the manufacturer of the connector for the connector to wall
clearance or the clearance listed in this manual.
Mobile home installations must use the the reduced
clearance connector clearances listed in this manual under
“Additional Requirements for Mobile Home Installations”.
Minimum System 15' (4.57M)
Maximum System 33' (10.05M)
Floor
Protection
Figure 5
Drafting
Performance
Draft is the force which moves air from the appliance up through the chimney. The amount
of draft in your chimney depends on the length of the chimney, local geography, nearby
obstructions and other factors. Too much draft may cause excessive temperatures in the
appliance and may damage the heater. Inadequate draft may cause backpuffing into the
room and `plugging' of the chimney. Inadequate draft will cause the appliance to leak
smoke into the room through appliance and chimney connector joints. An uncontrollable
burn or excessive temperature indicates excessive draft.