Specifications

34
Set for Power Supply Side
Set for Load Side
Caution Precaution for Correct Use
When the Magnetic Contactors are switched rapidly, use an
electrically interlock, such as a delay relay, to ensure a switching
time of at least 15ms for the contacts of the two Magnetic
Contactors.
Mechanical Interlock Unit
Interlock Unit
(1) Connect two Magnetic Contactors with the two connection
pieces .
(2) Move the moveable projections on the Interlock Unit to the
right side.
(3) Insert the Interlock Unit directly from the top so that it is aligned
with the projections on the moveable portion on the Magnetic
Contactors.
(4) After you mount the Interlock Unit, slide the projection on the
indicator window on the right side and then on the left side to
confirm that they move smoothly.
Power Connection Kit for Reversing
Connect the Kit to the main circuit terminals. There are wires for the
power supply side and wires for the load side. Be sure to connect
them to the correct sides.
Power Connection Kit for Reversing
Mechanical Interlock Unit: Joins two Magnetic Contactors to mechanically lock them.
Product name Used with Type
Mechanical Interlock Unit SK06, SK09, and SK12
SZ1KRM
Power Connection Kit for Reversing: Used to reverse the circuit wiring between the main circuit terminals.
Product name Wire size Number of conductors per set Used with Type
Power Connection Kit
for Reversing
AWG14 (1.6 dia.) One set for power supply side
One set for load side
SK06, SK09, and SK12
SZ1KRW1W
Mass : 8g Mass : 7g
Approx. 66.5
62.9
45.5
28.1
Approx. 66.5
62.9
45.5
28.1
* Connect the Contactors on the bottom side
in the same way.
Wires for
Load Side
Wires for
Power Supply Side
1 3 5
2 4 6
1 3 5
2 4 6
Mini-Contactors
SK Series
Mechanical Interlock Unit and Power Connection Kit for Reversing
Features
Mechanically prevent two Magnetic Contactors from turning ON at
the same time.
Combine a Reversing Connection Kit with an Interlock Unit to easily
configure a reversing Magnetic Contactors.
Mounting two Magnetic Contactors on the front surface reduces the
mounting footprint and contributes to downsizing control panels.
Types
Dimensions, mm
Mounting Procedures
Mechanical Interlock Unit and
Power Connection Kit for Reversing
83.8 Mass : 11g
22
7
SZ1KRM SZ1KRW1W