Specifications
3
Easier Wiring
①
Connection to Round Crimp Terminals
②
Terminal Arrangement for No Interference between Power Lines
for Main and Auxiliary Circuits When Wiring
Transparent cover
・
Dial lock.
・
Protects against unintentional
changes on the reset method.
Thermal Overload Relays: TK12
Auxiliary Relays: SKH4
Comparison with FUJI SJ Series
Footprint
Volume
45mm
97. 5mm
55mm
Main
terminals
Main
terminals
Auxiliary
terminals
TK12
The difficulties in wiring caused by
the previous terminal arrangement
have been eliminated.
Previous Models
The main circuits were difficult to wire
because the screwdriver had to be held
at an angle due to interference from the
auxiliary circuits.
Downsizing
Both AC-operated and DC-operated (2.4W and 1.2W) models are available and have the
same shape as the Magnetic Contactors.
Add up to eight contacts with the addition of Auxiliary Contact Blocks (2-pole or 4-pole).
A compact, 2-pole Auxiliary Contact Blocks with a reduced depth dimension is also available.
High Reliability and Safety
Lineup includes models with bifurcated contact for high reliability (standard models) and high-
capacity models (single button contact).
Auxiliary Relays with linked contacts.(Complies with requirements of IEC60947-5-1 Annex L.)
Contact specifications
[arrangement]
High-reliability
(standard) models
[bifurcated contact]
High-capacity
models
[single button contact]
Type SKH4
□
SKH4
□
H
Conventional free air thermal current
(Rated continuous current)
10A 10A
Coil load and rated
operational current
(AC-15)
100-120V 3A 6A
200-240V 3A 6A
380-440V 1A 6A
500-600V 0.5A 3A
Minimum voltage and current 5V DC, 3mA 24V DC, 10mA
Linked contact
○
45mm
48mm
49mm
Downsizing
Combine a Thermal Overload Relay with a Magnetic Contactor for
Meaningful Downsizing
Enhanced Safety
2E Thermal Overload Relay overload and phase-loss protection
with standard models.
A standard-feature transparent cover that serves as a dial lock
and that also protects against unintentional operation of the reset
button.
Standard-feature
easy-to-remove
terminal cover.
NEW
87% of
previous models
55% of
previous models
SK Series
SK06, SK09, and SK12