Specifications
20
Standard Operating Conditions
Ambient
temperature *1
−10 to 55°C with no sudden temperature changes resulting in condensation or icing (The average temperature over a
24-hour period must not exceed 35°C.)
Ambient humidity 45% to 85% RH (with no condensation)
Altitude 2,000 m max.
Atmosphere No excessive dust, smoke, corrosive gasses, inflammable gases, steam, or salts
Storage temperature −40 to 60°C
Vibration resistance 10 to 55Hz, 15m/s
2
Shock resistance 50m/s
2
Mounting
Screw mounting
35mm-wide top hat rail (Refer to the rail mounting in the next item.)
Mounting angle
30°
30°
30°
30°
Mounting gaps *2 Provide the mounting gaps and arc space that are given in the following table when you mount the product.
A[mm] B[mm] C[mm]
0 10 2
C
BAB
Grounded
plate
Grounded
plate
Grounded plate
or
insulation
Note *1: The ambient temperature is the temperature near the product during operation.
Note *2: If Magnetic Starters are used in combination with Thermal Overload Relays and the products are used with continuous through current without providing
gaps, temperature increases will reduce the life of the coil.Also, the characteristics of the Thermal Overload Relays will vary somewhat from the mutual
thermal effects between the heaters.When using the products under these conditions, separate the products from each other by at least 5 mm (dimension A).
Mounting Rail
Type TH35-15AL
Material Aluminum
External
dimensions
27
900
35
15
1
10
20
44×20=880
12
5.5
20
25
Rail Mounting
The SK06 to SK12 Magnetic Motors and
Starters can be mounted to 35mm-wide
support rails. Secure the rail with the
mounting pitch that is shown in the figure
at the right.
Example of Applicable Rail: TH35-15AL
Voltage Fluctuation Range in Control Circuits and Voltage Drop
SK06 to SK12A (AC Operation)
Drop-out voltage (operating voltage): 85% to 110% of rated voltage
However, there is an official rated inrush voltage, but usage is possible
without contact welding even if the voltage drops to 75% of the rating
when the main contacts close.
SK06 to SK12G, L-shape Drop (DC Operation)
Drop-out voltage (operating voltage): 85% to 110% of rated voltage
at ambient temperature of 55°C and 80% to 110% of rated voltage at
ambient temperature of 40°C.
However, there is an official rated inrush voltage, but usage is possible
without contact welding even if the voltage drops to 75% of the rating
when the main contacts close.
Mini-Contactors
SK Series
Normal Operating Conditions and Mounting
Normal Operating Conditions and Correct Mounting
M5
400 mm max.