Specifications

18
Combination of Breaker and Fuse
Magnetic Starter Short-circuit Current Ratings (SCCR)
Magnetic
Contactor
Thermal Overload Relay 240V AC 600V AC
Type Type Ampere
setting range
[A]
SCCR
[kA]
Circuit breaker SCCR
[kA]
Current-limiting fuse
Max. rated
current
[A]
UL489-certified
FUJI Automatic Breaker /
Earth Leakage Circuit Breaker
Max. rated current
[A]
SK06 TK12
0.1-0.15 25 15 BW125JAGU, BW125RAGU
EW125JAGU, EW125RAGU
5 30
0.13-0.2 25 15 5 30
0.18-0.27 25 15 5 30
0.24-0.36 25 15 5 30
0.3-0.45 25 15 5 30
0.34-0.52 25 15 5 30
0.48-0.72 25 15 5 30
0.64-0.96 25 15 5 30
0.8-1.2 25 15 5 30
0.95-1.45 25 15 5 30
1.4-2.1 25 20 5 30
1.7-2.6 25 20 5 30
2.2-3.4 25 20 5 30
2.8-4.2 25 20 5 30
4-6 25 20 5 30
SK09 TK12
0.1-0.15 25 15 BW125JAGU, BW125RAGU
EW125JAGU, EW125RAGU
5 30
0.13-0.2 25 15 5 30
0.18-0.27 25 15 5 30
0.24-0.36 25 15 5 30
0.3-0.45 25 15 5 30
0.34-0.52 25 15 5 30
0.48-0.72 25 15 5 30
0.64-0.96 25 15 5 30
0.8-1.2 25 15 5 30
0.95-1.45 25 15 5 30
1.4-2.1 25 20 5 30
1.7-2.6 25 20 5 30
2.2-3.4 25 20 5 30
2.8-4.2 25 20 5 30
4-6 25 20 5 30
5-7.5 25 20 5 30
6-9 25 20 5 30
SK12 TK12
0.1-0.15 25 15 BW125JAGU, BW125RAGU
EW125JAGU, EW125RAGU
5 30
0.13-0.2 25 15 5 30
0.18-0.27 25 15 5 30
0.24-0.36 25 15 5 30
0.3-0.45 25 15 5 30
0.34-0.52 25 15 5 30
0.48-0.72 25 15 5 30
0.64-0.96 25 15 5 30
0.8-1.2 25 15 5 30
0.95-1.45 25 15 5 30
1.4-2.1 25 20 5 30
1.7-2.6 25 20 5 30
2.2-3.4 25 20 5 30
2.8-4.2 25 20 5 30
4-6 25 20 5 30
5-7.5 25 20 5 30
6-9 25 20 5 30
7-10.5 25 20 5 30
9-13 25 30 5 30
SK06
25 30 BW125JAGU, BW125RAGU
EW125JAGU, EW125RAGU
5 30
SK09
25 30 5 30
SK12
25 30 5 30
Mini-Contactors
SK Series
Protective Coordination
UL approved Short-circuit Current Ratings (SCCR)