Specifications

16
Prospective Short-circuit Current “r” (240V and 440V)
Magnetic
Contactor
Thermal Overload Relay Coordination type
Type 1 Type 2
Type Type Ampere setting
range [A]
Short-circuit
current “r
[kA]
FUJI Automatic Breaker /
Earth Leakage Circuit Breaker
Short-circuit
current “r
[kA]
Fuse
(IEC 60269-1
gG and gM)
rating (A)
FUJI Low-voltage
Current-limiting Fuse
Type Rating [A] Type Rating [A]
SK06 TK12
0.34-0.52 1 BW32SAG
EW32SAG
3 1 2 BLA003 3
0.48-0.72 1 3 1 4 BLA005 5
0.64-0.96 1 5 1 4 BLA005 5
0.8-1.2 1 5 1 4 BLA005 5
0.95-1.45 1 10 1 16 BLA020 20
1.4-2.1 1 20 1 16 BLA020 20
1.7-2.6 1 20 1 16 BLA020 20
2.2-3.4 1 20 1 16 BLA020 20
2.8-4.2 1 20 1 16 BLA020 20
4-6 1 20 1 16 BLA020 20
SK09 TK12
0.34-0.52 1 BW32SAG
EW32SAG
3 1 2 BLA003 3
0.48-0.72 1 3 1 4 BLA005 5
0.64-0.96 1 5 1 4 BLA005 5
0.8-1.2 1 5 1 4 BLA005 5
0.95-1.45 1 10 1 16 BLA020 20
1.4-2.1 1 20 1 16 BLA020 20
1.7-2.6 1 20 1 16 BLA020 20
2.2-3.4 1 20 1 16 BLA020 20
2.8-4.2 1 20 1 16 BLA020 20
4-6 1 20 1 16 BLA020 20
5-7.5 1 20 1 16 BLA020 20
6-9 1 20 1 16 BLA020 20
SK12 TK12
0.34-0.52 1 BW32SAG
EW32SAG
3 1 2 BLA003 3
0.48-0.72 1 3 1 4 BLA005 5
0.64-0.96 1 5 1 4 BLA005 5
0.8-1.2 1 5 1 4 BLA005 5
0.95-1.45 1 10 1 16 BLA020 20
1.4-2.1 1 20 1 16 BLA020 20
1.7-2.6 1 20 1 16 BLA020 20
2.2-3.4 1 20 1 16 BLA020 20
2.8-4.2 1 20 1 16 BLA020 20
4-6 1 20 1 16 BLA020 20
5-7.5 1 20 1 16 BLA020 20
6-9 1 20 1 16 BLA020 20
7-10.5 1 20 1 16 BLA020 20
9-13 1 30 1 16 BLA020 20
Mini-Contactors
SK Series
Protective Coordination
Coordination with Short-circuit Protection Devices (SCPD) (Based on IEC and JIS Standards)