Specifications

13
AC-operated Models
Type Power consumption [VA] Watt loss [W] Pick-up voltage [V] Drop-out voltage
[V]
Operating times [ms]
SK06A
SK09A
SK12A
Inrush Sealed
Coil ON
Contact ON
Coil OFF
Contact OFF
200V
50Hz
220V
60Hz
200V
50Hz
220V
60Hz
200V
50Hz
220V
60Hz
50Hz 60Hz 50Hz 60Hz
22 25 4.5 4.5 1.2 1.3 122-135 128-138 80-89 83-96 17-26 8-11
Note 1. The characteristics are for the following coil ratings: 200V, 50Hz/200 to 220V, 60Hz.
Note 2. The electromagnet capacity is the same even when the rated coil voltage is not 200V AC.
Note 3. The operating times are for 200V AC, 50Hz.
Note 4. The pick-up voltage and drop-out voltage for a 100V (100V AC, 50 Hz/100 to 110V, 60Hz) coil are approximately half of the values that are given
in the above table.
Note 5. The values in the above table are examples for a cold status at 20°C.
DC-operated Models (2.4W)
Type Power consumption [W] Time constant
[ms]
Pick-up voltage [V] Drop-out voltage
[V]
Operating times [ms]
SK06G
SK09G
SK12G
Inrush Sealed Sealed
Coil ON
Contact ON
Coil OFF
Contact OFF
24V 24V
2.4 2.4 20 10 -11 4-6 22-24 5-6
Note 1. The characteristics are for the following coil rating: 24V DC.
Note 2. The electromagnet capacity is the same even when the rated coil voltage is not 24V DC.
Note 3. The values in the above table are examples for a cold status at 20°C.
DC-operated Models (1.2W)
Type Power consumption [W] Time constant
[ms]
Pick-up voltage [V] Drop-out voltage
[V]
Operating times [ms]
SK06L
SK09L
SK12L
Inrush Sealed Sealed
Coil ON
Contact ON
Coil OFF
Contact OFF
24V 24V
1.2 1.2 20 13-14 4-5 30-33 8-9
Note 1. The characteristics are for the following coil rating: 24V DC.
Note 2. The electromagnet capacity is the same even when the rated coil voltage is not 24V DC.
Note 3. The values in the above table are examples for a cold status at 20°C.
Operating Coil Characteristics
Mini-Contactors
SK Series
Ratings