User guide

In the Event of a Fire Alarm -
with Alarm Delay
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FB/FE Rev. A, 010531,
Autronica Fire and Security AS
Page 21
Step Actions to be taken Display Indication Audible Indication
5b
To silence all alarms,
press the red Silence
Alarms button.
SILENCE
19:23
Total: 3
Info: Completed
FIRE ALARMS Total: 1
1 KITCHEN
19:23
FIRE ALARMS
19:23
Total: 1
1 KITCHEN
All Fire Alarm Devices
(FAD) are deactivated.
Comments: The red FIRE indicator goes steady.
The alarm zones previously in alarm state are automatically resounded to
their alarm state on timeout of the silence resound timer.
When the fire is extinguished and all necessary repair work have been
carried out (smoke is exhausted, new glass replaced in the manual call-
points, etc.), the system should be returned to normal operating mode.
The SILENCE ALARMS button has to be pressed before pressing the
RESET button. Otherwise the reset operation will be rejected without having
any effect on system behaviour.
By means of the SILENCE ALARMS button, you can manually resound the
alarm zones at this stage.
6b
Press the green Reset
button.
RESET
19:23
Total: 3
Info : Completed
19:23
The audible indicator
on all panels within
the operation zone of
the Repeater Panel is
turned off.
Comments:
If there are no points signalling a fire alarm, the system is reset.
The red FIRE indicator goes off.
The red Fire Brig. Signalled indicator goes off.
AUTROSAFE
SelfVerify
If there are points still signalling a fire alarm, refer to step 6 in the procedure
described in the previous chapter.