User guide

Operation Mode
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FB/FE Rev. A, 010531,
Autronica Fire and Security AS
Page 14
3.9 Alarm Disablement (AlarmDisable)
If there are points within an operation zone still signalling a Fire Alarm
after the reset button has been pressed, an alarm disablement will
take effect.
Alarmdisabling may or may not be required to be confirmed by the
operator (configurable).
If confirmation is not required, all points still signalling a Fire Alarm,
are automatically disabled.
If confirmation is required, a list of points in alarm is presented on
the display. To confirm automatic disablement, the Reset button
must be pressed within 5 seconds (configurable).
The alarmdisabled detectors cannot be reactivated with the Repeater
Panel. This can be done by means of the Fire Alarm Control Panel BS-
320 or Operator Panel BS-330.