3.9 Alarm Disablement (AlarmDisable)
If there are points within an operation zone still signalling a Fire Alarm
after the reset button has been pressed, an alarm disablement will
take effect.
Alarmdisabling may or may not be required to be confirmed by the
operator (configurable).
• If confirmation is not required, all points still signalling a Fire Alarm,
are automatically disabled.
• If confirmation is required, a list of points in alarm is presented on
the display. To confirm automatic disablement, the Reset button
must be pressed within 5 seconds (configurable).
The alarmdisabled detectors cannot be reactivated with the Repeater
Panel. This can be done by means of the Fire Alarm Control Panel BS-
320 or Operator Panel BS-330.