User guide
Troubleshooting
Commissioning Handbook, AutroSafe Interactive Fire Alarm System, Release 3, P-ASAFE/EE Rev. E, 2005-02-16,
Autronica Fire and Security AS
Page 32
7. Troubleshooting
7.1 Distributed System
7.1.1 AUTROLON Service Diode Status After Reset
Location of
Diode(s)
Indication Status Actions to be taken
Display Board
BSR-310 on
BS-320
Steady red light.
(V32)
Normal indication after
reset.
-
Display Board
BSR-310 on
BU-320
BV-320
BS-330
Light turned off.
(V32)
Normal indication after
reset.
-
LON Interface
Board
EAU-310 on
BS-320, BC-320
After two short beeps are
heard, both LEDs should
turn off.
(V33 and V53)
Normal indication after
reset.
-
LON Interface
Board
EAU-310 on
BS-320, BC-320
Steady light.
(V33 and V53)
Flash Memory missing or
system not operating.
Insert Flash device(s) in
correct position(s). Repeat
the entire startup and
initialization procedure.
LON Interface
Board
EAU-310 on
BS-320, BC-320
Blinking rapidly.
(V33 and V53)
LON Interface not
communicating.
Repeat the entire startup
and initialization procedure.
BSR-310 Board
(BU/BV-320, BS-
330)
Steady light.
(V32)
Flash Memory missing or
system not operating.
Insert Flash device(s) in
correct position(s). Repeat
the entire startup and
initialization procedure.
LON Interface
Board
(BU/BV-320, BS-
330)
Blinking rapidly. LON Interface not
communicating.
Repeat the entire startup
and initialization procedure.
Display Board BSR-310
LON Interface Board EAU-310