Verifying System After Download
Commissioning Handbook, AutroSafe Interactive Fire Alarm System, Release 3, P-ASAFE/EE Rev. E, 2005-02-16,
Autronica Fire and Security AS
Page 31
6. Verifying System After Download
To ensure that the system works properly during normal operation,
the whole system (control panel, detectors, control functions) should
be verified after download.
Step Description
1
Test the panel indicator lights and internal buzzer by pushing the Mute button more
than 5 seconds.
2
Test all operating keys by pressing each key:
The following buttons will give a short "Beep" when pressed:
All the alphanumeric buttons, plus;
the red Silence Alarms , Cancel
C
, Enter , Help
i
, Close
The green Reset button
should reset the system (requires access level 3), or start the
lamptest (access level 1), by pressing it for more then 5sec.
The Menu button
should allow you to switch between Menu Mode and Operation
Mode.
3
Perform a visual and functional inspection of manual call-points and automatic detectors.
4
Disable any alarm transference to the Fire Alarm Routing Equipment -FARE output.
5
Activate the alarm system. Test all sounders by activating an alarm from a corresponding
manual call-point.
6
Test all control functions.
7
Activate alarms from at least one detector/manual call-point in each zone and a check that
all respective outputs are activated.
8
Test the action of any auxiliary operating functions (disabling, cancelling and resetting
buttons).
9
Check the alarm transference outputs by connecting from outgoing outputs (potential free
relay and 24V output) activated by alarm in a zone.
10
Check the fault warning function from detection zones by removing a detector in the
corresponding zone.
Activate a fault (remove battery fuse) and observe:
- the Fault indicator starts to blink
- a fault warning is displayed
- the internal buzzer is turned on
- the Fault Warning Routing Equipment (FWRE) output is activated (if any)
11
Verify all conditions, i.e.:
- Fire Alarm condition
- Fire Warning condition
- Fault Warning condition
- Disablement condition
- Test condition
12
On completion of checks, ensure that only the green "Power" indicator is on when the panel
is in its idle state (normal operation).
13
Enable alarm transference to the Fire Alarm Routing Equipment -FARE output.