User guide

Commissioning Handbook, AutroSafe Interactive Fire Alarm System, Release 3, P-ASAFE/EE Rev. E, 2005-02-16,
Autronica Fire and Security AS
Page 26
4.3.7 Booting the System from the Fire Alarm Control Panel BS-320
(Booting Panel)
The initialization of the system is done from the Fire Alarm Control
Panel (the booting panel). Refer to chapter
4.2.4 and 4.2.5.
When the downloading procedure is complete and the reset button on
the Display Board BSR-310 is pressed, the following will appear on
the booting panel's screen (example):
15:10
Starting
Paneltype = BS-
System SW
=x.x.x
Config interface
=x.x.x
Systemid =
01 (Switch S102
RingId=
01 (Switch S17
Waiting for AUTROLON
1: Start
To start AUTROLON, press digit 1 (Action Digit) on the
alphanumeric keyboard.
As soon as digit 1 has been pressed, the booting of the distributed
system will start. The system units are polled by the Booting Panel. At
this stage, only the network function is started. No AutroSafe system
functions are involved, and no configuration data is yet involved. The
interface version is checked.
The display will show the number of panels that are found. When the
AUTROLON start is complete, the following is shown in the bottom
information field:
1: Initialize AutroSafe
2: View AUTROLON topology