4.3.6 Downloading Configuration Files
• When downloading configuration data to the different system units
in a distributed system, make sure to download the configuration
files from the correct folders (see previous chapter).
• After download, do the following:
− move the jumper on the Display board BSR-310 back to its
original position (applies to all panels with display)
− move the jumper on the Processor Board EAC-300 back to its
original position (applies to BS-320/BC-320)
− press the Reset button (X1) on the Processor Board EAC-300
(applies to the Controller BC-320)
− press the Reset button on the Display Board (applies to all
panels with display)
− press the Reset button (S5) on the Display Board on the
Booting Panel (always the last system unit to reset)
When all system units are ready for initialization, the following will
appear on the screen on each system unit, except for the Controller
which has no display*):
15:10
Starting
Paneltype = BU-
System SW
=x.x.x
Config interface
=x.x.x
Systemid = 61 (Switch S102
Waiting for AUTROLON
The example above shows a Repeater Panel BU-320 (If such a
screen picture is not shown, press the reset button once more. The
version is indicated with x.x.x in this example.
* To make sure the Controller is ready for initialization, verify that the relay
on the BSF-310 clicks twice rapidly.