User guide
Commissioning Handbook, AutroSafe Interactive Fire Alarm System, Release 3, P-ASAFE/EE Rev. E, 2005-02-16,
Autronica Fire and Security AS
Page 23
4.3.3 Configuration Files
The AutroSafe Configuration Tool generates the following
configuration files:
System Unit Configuration Files (binary)
Fire Alarm Control Panel BS-320 BsrFlash.bin
EacEeprom.bin
EacFlash.bin
Controller BC-320 EacEeprom.bin
EacFlash.bin
Operator Panel BS-330 BsrFlash.bin
Repeater Panel BU-320 BsrFlash.bin
Information Panel BV-320 BsrFlash.bin
When the configuration files are generated, they are automatically
sorted in different folders in the Installation/Config_Bin directory.
Each folder indicates;
• the type of system unit (for example, BS-320)
• the Ring ID (hexadecimal numbers, for example, 01)
• the System ID (hexadecimal numbers, for example, 01)
Example:
The folder for a Fire Alarm Control Panel will typically have the
following identification:
BS-320_01_01
System Unit RingID SystemID