User guide

Commissioning Handbook, AutroSafe Interactive Fire Alarm System, Release 3, P-ASAFE/EE Rev. E, 2005-02-16,
Autronica Fire and Security AS
Page 18
4.2.5 Number Series - System ID and Ring ID
Note that in a standalone system where BS-310 is used, the switches
must be set to 0 for the System ID and the Ring ID.
As there can be several system units of the same type in a distributed
system, for example, two Operator Panels, three Information Panels
etc, there are defined System ID number series for each System Unit
type.
A general rule is that the Fire Alarm Control Panel, which is
considered as the Booting Panel, is always given System ID = 01.
The Ring ID is used to address the Fire Alarm Control Panel to the
AUTROLON ring. The Ring ID for a single AUTROLON ring is always
Ring ID = 01.
* Several AUTROLON rings can be interconnected as Multiple AUTROLON rings.
The Ring ID is used to address the Fire Alarm Control Panel to the correct
AUTROLON ring. This handbook deals with a single AUTROLON ring only.
The number series for System ID's for all System Units and the Ring
ID for the Fire Alarm Control Panel are listed in the table below. The
table gives hexadecimal values (the prefix 0x is not used in the
hexadecimal notation).
Number Series
System ID no. series Ring ID no. Series*
System Unit Hexa-decimal
Hexa-decimal
Fire Alarm Control
Panel (BS-320)
01 (Booting Panel)
01 -20
01
Controllers
(BC-320)
21 - 40
Operator Panels
(BS-330)
41 - 60
Repeater Panels
(BU-320)
61 - A0
Information Panels
(BV-320)
A1 - E0
The number series for each switch are listed in the table below.
Switchsettings
Switches
BSR-310 board BSZ-310 board
System Unit S102 S101 S17 S16
Booting Panel:
Fire Alarm Control
Panel (BS-320)
0 - 2
0 - F
0
1
Controllers
(BC-320)
2 - 4
0 - F
Operator Panels
(BS-330)
4 - 6
0 - F
Repeater Panels
(BU-320)
6 - A
0 - F
Information Panels
(BV-320)
A - E
0 - F