User guide

Commissioning Handbook, AutroSafe Interactive Fire Alarm System, Release 3, P-ASAFE/EE Rev. E, 2005-02-16,
Autronica Fire and Security AS
Page 17
4.2.3 Addressing System ID on Controllers
System ID numbers are set by means of two rotary switches (S17 and
S16) on the Operator Board BSZ-310 (see illustration below).
4.2.4 Addressing Ring ID on the Fire Alarm Control Panel (Booting Panel)
Note that only the Fire Alarm Control Panel (Booting Panel) must be
given a Ring ID.
The Ring ID number is set by means of two rotary switches (S17 and
S16) on the Operator Board BSZ-310 (see illustration below).
Rotary switches on the Operator Board
Rotary switches on the Operator Board
NOTE!
When setting hexadecimal numbers on the two rotary switches
on the Operator Board, always read the numbers from left
towards right, i.e. from S17 to S16 (except addresses 02=S17=0,
S16=2).
NOTE!
When setting hexadecimal numbers on the two rotary switches
on the Operator Board, always read the numbers from left
towards right, i.e. from S17 to S16.