User guide

System Menu
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. I, 2009-02-27,
Autronica Fire and Security AS
Page 82
13.8 How to Initialize the Fire Alarm System
The AutroSafe Interactive Fire Alarm System is automatically
initialized when the panel is turned on. However, in certain cases it
may be necessary to manually initialize the panel. In situations where
the loop topology has been changed in some way, for example, two
detectors have changed places or have been removed, a service
command (Clear Topology) has to be executed. When this command
is completed, the control panel has to be initialized manually.
The procedure below describes how to manually initialize the fire
alarm system.
Step Actions to be taken Display Indication
1
To enter the Main Menu, press
MENU
19:23
Total: 3
1 SHOW STATUS
2 DISABLE
3 ENABLE
4 SYSTEM
5 SERVICE
2
To select SYSTEM, press 4.
3
To select INITIALIZE, press 6.
4
To start the initialization, press
Comments: The initializing procedure will start, and is
completed when the message «Completed» is
shown in the display. To return the System
Menu, press the Close button.
SYSTEM
1 DATE AND TIME
2 INFORMATION
3 ACCESS LEVEL 3
4 PRINTER
5 CHANGE LANGUAGE
6 INITIALIZE
7 DAY/NIGHT TIMERS
19:23
SYSTEM
1 DATE AND TIME
2 INFORMATION
3 ACCESS LEVEL 3
4 PRINTER
5 CHANGE LANGUAGE
6 INITIALIZE
7 DAY/NIGHT TIMERS
19:23
SYSTEM
INITIALIZE
Start INIT
Phase 1:
Phase 2:
Phase 3:
Phase 4:
Info: Completed