6.2 Ex. 2: Multiple Branch-off (Star-connection)
In this example, the LoopViewer has given a warning between LSI 19
and 21. This is to indicate that when closing LSI 19’s switch, more
than 2 new points where powered up. The LoopViewer cannot present
more than 3 points in a star-connection, and since more than 1
branch-off is illegal in an AutroSafe system, this warning is given.
So in this case, LSI-21, LSI-19.1 and LSI-20.1 are connected to the
same point, LSI-19. A possible solution to this problem, would be to
connect branch 19.1 to 19.2 between the manual callpoint (LSI18) and
the Multisensor (LS19).
Note that the LoopViewer cannot present more than 3 points in a star-
connection. If there were more than LSI-21, LSI-19.1 and LSI-20
connected to LSI-19, these additional would not be presented in the
topology window.