User guide
Service and Maintenance 
Installation Handbook, AutroSafe Interactive Fire Alarm System, Release 3, 116-P-ASAFE-FA/DE, 
Rev. J, 2011-12-06, 
 Autronica Fire and Security AS 
The whole system (control panel, detectors, control functions) should 
be inspected annually. In addition to a system restart, an annual 
service inspection comprises the following: 
Step  Description 
1 
Test the panel indicator lights and internal buzzer by pushing the Mute button more than 5 
seconds. 
2 
Test all operating keys by pressing each key: 
The following buttons will give a short "Beep" when pressed: 
All the alphanumeric buttons, plus; 
the red Silence Alarms 
, Cancel 
C
, Enter   , Help 
i
 , Close  
The green Reset button 
 should reset the system (requires access level 3). 
The Menu button 
 should allow you to switch between Menu Mode and Operation Mode. 
3 
Perform a visual and functional inspection of manual call-points and automatic detectors. 
4 
Activate the alarm system. Test all sounders by activating an alarm from a corresponding 
manual call-point. 
5 
Test all control functions. 
6 
Disable any alarm transference to the Fire Alarm Routing Equipment -FARE output. 
7 
Activate alarms from at least one detector/manual call-point in each zone and a check that all 
respective outputs are activated. 
8 
Test the action of any auxiliary operating functions (disabling, cancelling and resetting 
buttons). 
9 
Check the alarm transference outputs by connecting from outgoing outputs (potential free 
relay and 24V output) activated by alarm in a zone. 
10 
Check the fault warning function from detector zones by removing a detector in each zone. 
Activate a fault (remove battery fuse) and observe: 
- the Fault indicator starts to blink 
- a fault warning is displayed 
- the internal buzzer is turned on 
- the Fault Warning Routing Equipment (FWRE) output is activated (if any) 
11 
Verify all conditions, i.e.: 
- Fire Alarm condition 
- Fire Warning condition 
- Fault Warning condition 
- Disablement condition 
- Test condition 
12 
Check the battery voltage by disconnecting the charger and measure the voltage across the 
battery after approx. 1-2 minutes (depending on the load). The voltage should be >24.5V. 
13 
On completion of checks, ensure that only the green "Power" indicator is on when the panel 
is in its idle state (normal operation). 
14 
Complete a service report and service log. 
The battery should be changed every 4 years. If a fault arises on the 
panel that cannot be rectified, contact your nearest Autronica Fire and 
Security office for qualified assistance. 