User guide
Interfacing AutroMaster_5000 
Installation Handbook, AutroSafe Interactive Fire Alarm System, Release 3, 116-P-ASAFE-FA/DE, 
Rev. J, 2011-12-06, 
 Autronica Fire and Security AS 
5.3  Application with several AUTROLON rings 
5.3.1 General 
AutroMaster 5000 is used as the top level system. AutroMaster 5000 
enables a two-way communication with both AUTROLON rings and 
monitors the entire system. 
NOTE: 
The communication is not possible through AUTROLON rings by use 
of AutroMaster 5000. The connection from the panels on each 
AUTROLON ring is done via TP or optical fibre and a HUB to 
AutroMaster 5000. 
The units BN-300 (Fire Alarm Interface Unit) and BN-310 (Relay 
Output Unit) are used to identify a limited number of alarms between 
the AUTROLON rings. For this purpose a detection loop on 
AUTROLON ring 1 is connected to a detection loop on AUTROLON 
ring 2. 
Output (FPE; Fire Protection Equipment) on the BN-310 unit on 
AUTROLON ring 2 is connected to input (FAI; Fire Alarm Interface) on 
AUTROLON ring 1 (or opposite). By means of the AutroSafe 
Configuration Tool, FPE on AUTROLON ring 2 is connected to 
detection zones (DZ's), which enables alarm transfer to FAI on 
AUTROLON ring 1. FAI on AUTROLON ring 1 is connected to a 
Patchcable 
The Ethernet Communication 
Board, EAU-330 with a 
Patchcable connected.