User guide
Internal Cable Connections 
Installation Handbook, AutroSafe Interactive Fire Alarm System, Release 3, 116-P-ASAFE-FA/DE, 
Rev. J, 2011-12-06, 
 Autronica Fire and Security AS 
2.8.2  Connecting the Cable to External Temperature Sensor 
When a solution with external battery connection is used, the sensor 
must be removed from the Power Supply BSS-103A/02. A 3m cable 
must then be connected between the Power Supply BSS-103A/02 in 
the Fire Alarm Control Panel / Controller and the external temperature 
sensor mounted on a connector in the Battery Cabinet SY-310. 
The cable for this purpose is delivered with the battery cabinet. For 
information on cable connections, consult the illustrations below. 
  Remove the front cover on the Power Supply BSS-103A/02 (in the 
Fire Alarm Control Panel / Controller). 
  Remove the temperature sensor.   
  Connect the cable from the Battery Cabinet to the connector on the 
Power Supply BSS-103A/02. 
  Reassemble the front cover on the Power Supply BS-103/01. 
Battery Cabinet
Power Supply 
BSS-103A/02 in 
Fire Alarm Control 
Panel or Controller
External
Power Supply 
BSS-103A/02 in 
Fire Alarm 
Control Panel 
or Controller 
Fasten 
cable 
with 
strips
Temperature
Sensor