User guide
Mounting 
Installation Handbook, AutroSafe Interactive Fire Alarm System, Release 3, 116-P-ASAFE-FA/DE, 
Rev. J, 2011-12-06, 
 Autronica Fire and Security AS 
Mounting 
1.7 Introduction 
This chapter deals with the following mounting alternatives: 
 Surface mounting 
  Flush mounting in a wall 
For surface mounting and flush mounting in a wall, a stand-alone 
cabinet is used. 
1.8 Location 
The Fire Alarm aControl Panel must be located in, or near by, the 
entrance. Both the Fire Alarm Control Panel and the Controller must 
be placed according to local regulations and in consultation with the 
fire brigade. 
1.9  Mounting Height / Space Requirement 
To ensure optimal readability of the Fire Alarm Control Panel's 
display, the recommended mounting height of this cabinet top is 
approximately 175 cm above the floor. 
For surface mounting and flush mounting in a wall, there must be a 
free space of minimum 50 mm from the cabinet top to the ceiling in 
order to fasten the top screw on the front panel door after the 
installation. A crosshead screwdriver can be used for this purpose. 