10.7 Upgrading Software Version 4.0.1 to 4.1.1
10.7.1 General
This chapter deals with the upgrade from software version 4.0.1 to
4.1.1.
Before reconfiguring the system or upgrading the system software, a
hardware reset must be executed. All panels belonging to the same
system will be reset and upgrading can then take place.
If the system is in normal operation, go to chapter 10.7.2.
If the system is in system fault condition, go to chapter 10.7.3.
10.7.2 Preparing a System in Normal Operation
Push the reset button S5 less than 1 second to shut down the
panel in a controlled manner.
Wait until the blue LED indicator D22 (see illustration on next page)
goes off.
The panel has now entered system fault condition.
Go to chapter 10.7.3.
IMPORTANT:
Follow the upgrade procedure as described in detail below.
During the upgrade to software version 4.1.1, the system will
enter system fault condition.
Do NOT disconnect the mains power or press the front panel’s
Reset System button.
Press the front panel’s Mute button to silence the buzzer.
Note that a panel that has been upgraded to software version
4.1.1 cannot
be downgraded to software version 4.0.1.