User guide

Startup Procedure
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.D, 2011-09-14,
Autronica Fire and Security AS
Page 23
8.2 IP Number Structure
Example:
172.16.101.21
172.17.101.117
172.16.101.21
8.3 Assigning IP Adresses
When the initialization is completed, the display will show the
following:
Autrosafe software version 4.3.1
Config model 4.4
Market version: Land
Switch address 01-001
Searching for panels, found 2
BS-420 01.01: 4.3.1
BU-420 01.01: 4.3.1
IP not set, select addressing mode:
1. Automatic 2. Manual
If Automatic Mode is selected, default IP Adresses will be assigned to
each panel. The number series which is used depends on the switch
settings for the panel’s System ID.
Note:
Use automatic addressing mode if you are not absolutely sure how to
set IP addresses.
Panel ID (+20), unique ID assigned to each panel
System ID (+100), identifies which system and unique
configuration the panel belongs to.
Ethernet Port ID, referring to one of the two
redundant network ports (each panel assigned to two
consecutive numbers)
Network Number, common number for all panels
belonging to the same network