User guide

Startup Procedure
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.D, 2011-09-14,
Autronica Fire and Security AS
Page 22
8. Startup Procedure
When the AutroFieldBus units (Power Boards BSF-400 and all panels)
have been addressed, and the configuration files have been
generated by means of the AutroSafe Configuration Tool, power is to
be applied to the system.
The commissioning can take place from any Fire Alarm Control Panel
BS-420 or Operator Panel BS-430 in the system (freely selected
panel).
During uploading of configuration files (or system software), the
system may report possible faults. If such fault messages occur, the
panel in question should be rebooted (Service
Menu/Upgrade/Reboot). For detailed information on possible errors,
refer to chapter 12, Fault Messages during Uploading.
8.1 Applying Power to the System
Always connect the cables to the batteries first, then power up the
system by connecting the mains cable to a mains socket (230V/115V
AC) or by switching the power ON from an external main fuse box.
When power is applied to the system the very first time, an
initialization of the system will automatically take place.
Apply power to the system.
The display will show the following information (example):
Autrosafe software version 4.3.1
Config model 4.4
Market version: Land
Switch address 01-001
Searching for panels, found 2 of x
BS-420 01.01: 4.3.1
BU-420 01.01: 4.3.1
IP not set, select addressing mode:
1. Automatic 2. Manual
Note that, to prepare the system for later reconfigurations or software
upgrades, a hardware reset must be performed. Refer to Upgrading
the System, chapter 10.