User guide

Addressing Panels
Commissioning Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-COMMISS/EGB Rev.D, 2011-09-14,
Autronica Fire and Security AS
Page 19
6.4 Assigning Panel IDs
The settings of the rotary switches X6 and X4, plus the settings of dip-
switch S2 (type of panel) determine the Panel ID.
Each panel in the system must be assigned a unique Panel ID (switch
settings) which must correspond to the Panel ID given in the specific
configuration in the Configuration Tool.
Note that a standalone Fire Alarm Control Panel BS-420 always has
Panel ID=00.
Switch X6 corresponds to the most significant digit in the address.
Note that the correct switch settings for the panel type in question is
preset at the factory (dipswitch S2) - except for the BU-BV-420 panel,
as this panel can be defined both as a Information Panel and Fire
Brigade Panel.
The following table deals with the Panel IDs when several panels
communicate on the AutroNet (local area network).
Panel Panel ID
Panel ID
Hex.
values Rotary
switch X6
Rotary
switch X4
Panel Type
Dip-switch S2
0=OFF, 1=ON
Switch 1 2 3 4
BS-420 1-31
01-1F
0-3 0-9 0 0 0 0
BC-420 33-63
21–3F
0-3 0-9 1 0 0 0
BS-430 65-95
41-5F
0-3 0-9 0 1 0 0
BU-420 97-159
61-9F
0-6 0-9 1 1 0 0
BV-420 161-223
A1-DF
0-6 0-9 1 0 1 0
X6
X
4
S2