6. Addressing Panels
6.1 Definitions
6.1.1 System ID
A panel’s System ID indicates which system and unique configuration
a panel belongs to. All panels communicating on the same AutroNet
network must have the same System ID, usually set to 01 (switch
setting; rotary switches X5 and X3).
The System ID also determines the specific number series of the IP
Addresses (which are set during commissioning by operating the
AutroSafe menu).
Note that the term “Network ID” is used on the circuit board’s label instead of the correct
term System ID. In earlier AutroSafe 3 versions, Panel ID was used instead of System
ID.
6.1.2 Panel ID
Each panel in the system must be assigned a unique Panel ID which
must correspond to the Panel ID given in the specific configuration in
the Configuration Tool (switch setting; rotary switches X6 and X4, plus
the settings of dip-switch S2).
The Configuration Tool generates a catalogue structure with the
following number series of Panel IDs for the different panel types:
Panel
Panel IDs
Number Series
Panel IDs
Hexadecimal
values
BS-420 1-31 01-1F
BC-420 33-63 21–3F
BS-430 65-95 41-5F
BU-420 97-159 61-9F
BV-420 161-223 A1-DF
Note that term System ID is used in the configuration tool and on the circuit board’s
label instead of the correct term Panel ID.