User guide

Service Commands
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-OPERATE/FGB Rev. B, 2009-10-28,
Autronica Fire and Security AS
Page 72
16.7 Local Outputs
This chapter describes how to test each Local Output individually.
When the test is initiated for a selected local output, a test signal will
be sent to this output.
From the Service Menu, perform the following:
 Use the arrow down button to scroll downwards to
Unit Test, then press Enter.
 Press Enter once more.
 Use the arrow button to select the Local Output that
is to be tested. Use, if necessary, the multiselect feature to select
several local outputs.
 Press the Function button
 To start the test, press Enter.
 Press Enter once more to confirm.
 To stop the test, use the arrow button to select Stop Test, then
press Enter twice.
NOTE:
Before this test is performed
, make sure that all extinguishers
(or other similar equipment) that are to be tested are
disconnected. During the test, use a measuring instrument to
measure the output on the Fire Protection Equipment that is
to be tested.