Specifications

Switches and Indicators on
the Main Board
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-INSTALL/DGB Rev. E, 2011-08-16,
Autronica Fire and Security AS
Page 56
12.5 Battery Restart after Deep Discharge (S3)
The Battery Restart switch (S3) is to be pressed only in case you
need to commission the panel by means of the batteries (if the mains
power is not available). A complete hardware reset will take place.
The switch turns on the relay in the battery circuit.
If the system is run from battery and the battery is replaced, the
switch must be operated to restart the system
EN54 part 4 states that if the battery voltage drops below a limit
specified by the manufacturer (17V) the battery shall be disconnected
to prevent deep discharge. The battery is disconnected using a relay.
Battery
Restart
Switch
S
3