Specifications
Switches and Indicators on
the Main Board
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-INSTALL/DGB Rev. E, 2011-08-16,
Autronica Fire and Security AS
Page 55
12.3 Dip-switches for Mode Settings (S2)
Switch Description
S2.1 Boot select, if ON, boot from external memory, if OFF boot from
internal boot ROM. In normal operation set to On.
S2.2 Determines the panel variant:
BS-200 (standard variant): ON
BS-200M (maritime variant, SOLAS): OFF
BS-200L (agricultural applications): ON
S2.3 Multi-purpose serial port RS-485/RS-422 failsafe termination,
ON/OFF
S2.4
S2.5 Multi-purpose serial port RS-485/RS-422 line termination,
ON/OFF
S2.6 RS-485/RS-422 mode select, if ON, RS-485 mode, if OFF RS-422
mode
S2.7
S2.8 Must always be OFF.
12.4 Battery Short-circuit Protection
The battery circuit is protected with an automatic resettable electronic
fuse that prevents system shutdown in case of short-circuit in the
battery circuit.
Internal Cabling
Connector Description Power Supply
J3.1 Charge Control VCON
J3.2 Charge Control FB -V
J3.3 Mains OK PSF
J3.4 Battery Temperature
Sense +
Battery
Temperature
Sensor
J3.5 Battery Temperature
Sense -
J1.3 Charger +24V +V
J1.4 Charger 0V -V