Specifications
Cable Connections
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-INSTALL/DGB Rev. E, 2011-08-16,
Autronica Fire and Security AS
Page 36
9.8 Connection of Communication Cables inside the
Cabinet (Fire Alarm Control Panel)
CAUTION
9.8.1 Connection of internal communication cables in a standalone
cabinet
Delivered from the factory, the return/inputs (Input A and Input B) from
the integrated operater panel (BS-210) in a standalone cabinet are
connected at J4-18 and J4-19 as shown below.
J4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Output +24V
Output 0V
Output A
Output B
Input +24V
Input 0V
Input A
Input B
9.8.2 Connection of communication cables when additional panels are
connected on the Panel Bus
When additional panels (BU-, BV-, BS-panels, Mimic Drivers) are
connected on a panel bus, the following connections apply:
The return/inputs (Input A and Input B) from the integrated
Operator Panel (BS-210) must be connected at J4-14 and J4-15 as
shown below.
The communication cables to the external Panel Bus must be
connected as shown below (J4-16 to J4-19).
J4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
To Panel Bus
Output +24V
Output 0V
Output A
Output B
Input +24V
Input 0V
Input A
Input B
Output A
Output B
Input A
Input B
Do not connect the 24V wire to the terminal points used for
communication (A and B terminals). This will lead to
malfunction of the communication circuits.
!