Specifications
Cable Connections
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-INSTALL/DGB Rev. E, 2011-08-16,
Autronica Fire and Security AS
Page 34
J1-x Description Internal External
31
Detection
Loop2 in +
detectors/
loop units
32
Detection
Loop2 in -
9.7.2 Auxiliary Term inal Block J4
The auxiliary spring-loaded connection block J4 is capable of cables
up to 0,5mm
2
single or multi stranded cables. If multi stranded cables
are used, cable crimps should be used.
J4-x Description Internal External
1
Multifunction serial
port RS-232 TX
External Interface
Optional data lines
2
Multifunction serial
port RS-232 RX
3
Multifunction serial
port RS-232/422/485
0V
4
Multifunction serial
port RS-422/485 A
5
Multifunction serial
port RS-422/485 B
6
Multifunction serial
port RS-422 Z
7
Multifunction serial
port RS-422 X
8
Operator Panel
Output +24V
Connections to
Operator Panel
(Return/Input for
redundancy).
9
Operator Panel
Output 0V
10
Operator Panel
Output A
11
Operator Panel
Output B
12
Operator Panel Input
+24V
13
Operator Panel Input
0V
14
Operator Panel Input
A
Connections to
Operator Panel
(Return/Input for
redundancy).
If no additional
panels are
connected to the
panel bus,
return/input from
operater panel at
J4-18 and J4-19.
15
Operator Panel Input
B
16
BU/BV/Mimic Driver
Output A
Connections to
panel bus.
Connects from unit
to unit.
(Return/Input for
redundancy)
17
BU/BV/Mimic Driver
Output B
18
BU/BV/Mimic Driver
Input A