Specifications
Cable Connections
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-INSTALL/DGB Rev. E, 2011-08-16,
Autronica Fire and Security AS
Page 33
J1-x Description Internal External
18
Auxiliary1
+24V out
Same fuse
as J1.7
Supply
voltage for
loads
connected to
Open
collector
outputs 1
and 2.
Max.1A
19
Relay
Output 1
Com
20
Relay
Output 1
NO
21
Relay
Output 1
NC
Default
configured
as
Fire Alarm
Routing
Equipment.
(FARE)
Potential
free change-
over contact.
Non-
monitored.
Max.
30VDC/1A
22
Relay
Output 2
Com
(non-energized)
23
Relay
Output 2
NO
24
Relay
Output 2
NC
Default
configured
as (FWRE)
Fault
Warning
Routing
Equipment.
Potential
free change-
over contact.
Non-
monitored.
Max.30VDC/
1A
25
Detection
Loop1 out +
For
connection
of
Max 127
detectors/
loop units
26
Detection
Loop1 out -
27
Detection
Loop1 in +
28
Detection
Loop1 in -
29
Detection
Loop2 out +
For
connection
of
Max 127
30
Detection
Loop2 out -
25
26
27
28
29
30
31
32